Contact Us Now| Approvals | LPCB / CE-CPR |
| Operating Voltage | 20V to 28V DC |
| Current Parameters | Standby: 23mA, Commission: 56mA, Alarm: 33mA |
| Beam Sensor Sensitivity | Level 1: 2.6 dB High Sensitivity Level 2: 3.8 dB Medium Sensitivity Level 3: 5.8 dB Low Sensitivity |
| Beam Pathway Length | Span 1: 8 to 20 meters (Limited Path, 1× mirror reflector required) Span 2: 20 to 40 meters (Short Path, 1× mirror reflector required) Span 3: 40 to 70 meters (Normal Path, 4× mirror reflectors required) Span 4: 70 to 100 meters (Long Path, 4× mirror reflectors required) |
| Beam Path Angle | ±0.4° Directional |
| Alignment Guide | Laser Beam Pointer |
| Digital Display Guide | Nixie Tube |
| LED Indicator Guide | Red: Fire; Yellow: Fault; Green: Alignment |
| Reset Time | Less than 2 Seconds (Power Cut) |
| Relay Capacity [Fire/Fault] | Normally Open & Close / 2.0A; 30VDC |
| Material / Colour | ABS / White Glossy finishing |
| Dimension (L×W×H) | 190.87 × 126.87 × 91.96 mm |
| Weight | 1.1 kg with base |
| Accessories | Mounting Bracket / SK7130-R 4× Mirror Reflector (SK7930 sold separately) |
| Operating Temperature | -10°C to +50°C |
| Protection Rating | IP30 [IP66 glue seal-For permanent fixing, not EN54-12 approved) |